Voltix logoVoltix

Earthing & Grounding Conductor Calculator

NECBS 7671AS/NZS

Size the protective earthing conductor (CPC) under BS 7671 / AS/NZS, or the equipment grounding conductor (EGC) under the NEC. Switch standards with one tap - BS 7671 sizes from the line conductor, the NEC sizes from the overcurrent device.

Protective conductor (CPC)

16mm²

Minimum required

16mm²

16 mm² protective conductor

BS 7671 Table 54.7 - 16 < S ≤ 35 mm²: protective conductor = 16 mm².

Need more power?

The Voltix app gives you all 12 calculators, offline access, and built-in reference tables. Free to download - Pro unlocks everything.

GET IT ONGoogle Play
Coming soon toApp Store

Two standards, two methods

Earthing and grounding conductors carry fault current safely back to the source so the protective device can disconnect. The two main standards size them differently:

  • BS 7671 / AS/NZS size the circuit protective conductor (CPC) from the line conductor cross-sectional area via Table 54.7, or by the adiabatic equation S = √(I²t) ÷ k.
  • NEC sizes the equipment grounding conductor (EGC) from the overcurrent device rating via Table 250.122.

Worked examples

BS 7671:a 25 mm² line conductor falls in the 16–35 mm² band, so the CPC is 16 mm².

NEC:a circuit protected by a 100 A breaker requires an 8 AWG copper equipment grounding conductor.

Frequently Asked Questions

How is the CPC sized under BS 7671?
BS 7671 Table 54.7 relates the protective conductor to the line conductor: equal size up to 16 mm², 16 mm² for line sizes between 16 and 35 mm², and half the line size above 35 mm². The adiabatic equation may give a smaller result where calculated.
How is the equipment grounding conductor sized under the NEC?
NEC Table 250.122 sizes the EGC from the rating of the overcurrent device protecting the circuit - for example a 100 A breaker requires an 8 AWG copper EGC.
What's the difference between earthing and grounding?
They describe the same concept in different standards. 'Earthing' is the term used in BS 7671 and AS/NZS; 'grounding' is the NEC term. Both connect exposed metalwork to earth for safety.
Does the grounding conductor increase if I upsize the phase conductors?
Yes. NEC 250.122(B) requires the EGC to be increased proportionally when ungrounded conductors are upsized (for example for voltage drop). The Voltix app handles this adjustment automatically.

Related calculators

Take Voltix to the field.

Download the Android app and get 12 professional calculators, offline, always available, across NEC, BS 7671 and AS/NZS.

GET IT ONGoogle Play
Coming soon toApp Store