Voltix logoVoltix

Wire Size Calculator (NEC)

NEC

Find the correct wire size (AWG) for any circuit under the National Electrical Code (NEC). Based on NEC Table 310.16 conductor ampacity ratings at 60 °C, 75 °C, and 90 °C, with temperature and conduit-fill derating. Covers copper and aluminium conductors.

Minimum wire size

8 AWG

Base ampacity (75 °C)

50A

Derated ampacity

50A

8 AWG copper carries the load after derating

Ambient factor 1 × raceway factor 1 applied to the 75 °C column of NEC Table 310.16.

Remember NEC 240.4(D): 14 AWG is limited to 15 A, 12 AWG to 20 A, and 10 AWG to 30 A regardless of ampacity.

Need more power?

The Voltix app gives you all 12 calculators, offline access, and built-in reference tables. Free to download - Pro unlocks everything.

GET IT ONGoogle Play
Coming soon toApp Store

How NEC wire sizing works

Conductor selection starts with NEC Table 310.16, which lists the allowable ampacity of each AWG/kcmil size at three insulation temperature ratings. You then apply two adjustments:

  • Ambient temperature correction(Table 310.15(B)) - for ambient above 30 °C the ampacity is reduced.
  • Conductor bundling adjustment (Table 310.15(C)) - when more than three current-carrying conductors share a raceway, ampacity is reduced to 80%, 70%, 50% or 45%.

The terminal rule still applies: even if the 90 °C column is used for derating, the final conductor must be protected at no more than the ampacity of its terminal rating (usually 75 °C).

Worked example

A 40 A continuous load on 75 °C copper terminals, four conductors in a raceway at 30 °C ambient:

  • Conduit factor for 4–6 conductors = 0.80
  • 8 AWG copper (50 A at 75 °C) × 0.80 = 40 A - exactly at the load
  • For a continuous load, size at 125% → 50 A, requiring 6 AWG copper

Frequently Asked Questions

What is the minimum wire size for a 20-amp circuit (NEC)?
Per NEC Table 310.16, 12 AWG copper is rated 20 A at 60 °C and 25 A at 75 °C. For a 20-amp breaker, 12 AWG copper is the minimum.
Why does the NEC limit 14 AWG to 15 amps when the wire is rated for more?
NEC 240.4(D) applies the 'small conductor rule', limiting 14 AWG to 15 A overcurrent protection, 12 AWG to 20 A and 10 AWG to 30 A, regardless of the wire's temperature rating.
When should I use the 75 °C column vs the 60 °C column?
Use 75 °C for conductors connected to terminals rated 75 °C or higher (most modern breakers and panelboards). Use 60 °C for older equipment or when terminal ratings are unknown.
Does wire size affect voltage drop?
Yes. Larger wire has lower resistance and lower voltage drop. Use our Voltage Drop Calculator to check both ampacity and voltage drop for long runs.

Related calculators

Take Voltix to the field.

Download the Android app and get 12 professional calculators, offline, always available, across NEC, BS 7671 and AS/NZS.

GET IT ONGoogle Play
Coming soon toApp Store