Voltix logoVoltix

Voltage Drop Calculator

NECBS 7671AS/NZS

Calculate voltage drop across electrical conductors for any circuit. Select your electrical standard (NEC, BS 7671, or AS/NZS), enter your cable length, conductor size, and load current - and get instant voltage drop in volts and percentage. Free for any circuit type.

Voltage drop

10.51V

Percentage drop

4.57%

Acceptable (3–5%)

Acceptable for general circuits but close to the limit - consider a larger conductor for long runs or sensitive loads.

Need more power?

The Voltix app gives you all 12 calculators, offline access, and built-in reference tables. Free to download - Pro unlocks everything.

GET IT ONGoogle Play
Coming soon toApp Store

How voltage drop works

Voltage drop occurs when current flows through a conductor - the longer or thinner the cable, the higher the drop. In a 230 V circuit, a 3% voltage drop represents 6.9 V lost before it reaches your load. This matters for motor starting, lighting performance, and compliance with your wiring standard.

The formula (BS 7671 / AS/NZS)

Voltage Drop (V) = (mV/A/m × Current × Length) ÷ 1000

The mV/A/mfigure (millivolts per amp per metre) comes from the cable manufacturer's tables and depends on the conductor material and cross-sectional area. Three-phase circuits use a factor of 0.866 (√3 ÷ 2).

The formula (NEC)

Voltage Drop (V) = (2 × K × Current × Distance) ÷ Circular Mils

Where K = 12.9 for copper and 21.2 for aluminium, distance is the one-way run in feet, and the factor of 2 accounts for the out-and-back path of a single-phase circuit (three-phase uses 1.732).

Worked example

A 32 A circuit runs 45 metres of 6 mm² twin-and-earth copper cable at 230 V single phase (BS 7671). The mV/A/m figure for 6 mm² copper is 7.3:

  • Voltage Drop = (7.3 × 32 × 45) ÷ 1000 = 10.51 V
  • Percentage = 10.51 ÷ 230 = 4.57%

Result:acceptable, but close to the 5% BS 7671 limit. For a longer run or sensitive load, consider upgrading to 10 mm².

Frequently Asked Questions

What is the maximum voltage drop allowed by BS 7671?
BS 7671:2018 recommends a maximum voltage drop of 3% for lighting circuits and 5% for all other circuits, measured between the origin of the installation and the load.
What does the NEC say about voltage drop?
The NEC does not mandate a specific voltage drop limit but recommends (as an informational note) a maximum of 3% for branch circuits and 5% combined for feeders and branch circuits, for efficiency reasons.
Does voltage drop affect equipment performance?
Yes. Motors may fail to start or overheat if voltage is too low. LED drivers and sensitive electronics can malfunction. Always check voltage drop for long cable runs or high-current loads.
How do I reduce voltage drop?
Use a larger conductor size, shorten the cable run, increase the supply voltage, or split the load across multiple circuits. The Voltix app lets you compare options side by side.
Is voltage drop the same as voltage loss?
They're used interchangeably. Technically, voltage drop refers to the potential difference across the conductor's resistance - this energy is converted to heat in the cable rather than delivered to the load.

Related calculators

Take Voltix to the field.

Download the Android app and get 12 professional calculators, offline, always available, across NEC, BS 7671 and AS/NZS.

GET IT ONGoogle Play
Coming soon toApp Store