BS 7671 Wiring Regulations Reference
BS 7671 is the British Standard for the requirements for electrical installations - universally known as the IET Wiring Regulations. The current edition is BS 7671:2018+A2:2022 (the 18th Edition, incorporating Amendment 2), and compliance is the practical benchmark for safe, lawful electrical work across the United Kingdom. The Voltix calculators aimed at UK electricians follow its tables and correction-factor methodology directly.
Key tables for calculations
Cable selection under BS 7671 revolves around a small set of tables in Appendix 4 and the protection chapters. These are the ones you will reach for most often:
Tables 4A–4D - Current-carrying capacity and voltage drop
Appendix 4 contains the rating and voltage-drop data for cables. The current-carrying capacity tables (4D1A, 4D2A and similar) give the tabulated current (It) for each conductor size against its installation reference method, while the companion columns give the mV/A/m (millivolts per amp per metre) figure used to calculate voltage drop. The accompanying Tables 4A–4C define the installation reference methods and the rating-factor groupings.
Correction factors - Ca, Cg, Ci and Cc
The tabulated rating is rarely the rating you can actually use. BS 7671 applies correction factors to account for the installed conditions:
- Ca - ambient temperature, where the surroundings differ from the 30°C reference.
- Cg - grouping, where cables are bunched together and shed heat less effectively.
- Ci - thermal insulation, where a cable is surrounded by or in contact with insulation.
- Cc - the factor for circuits protected by a semi-enclosed (rewirable) fuse or buried in the ground.
The corrected rating Iz must satisfy Ib ≤ In ≤ Iz, where Ib is the design current and In is the nominal rating of the protective device.
Chapter 41 / Table 41 - Disconnection times
Chapter 41 covers protection against electric shock. Its disconnection time tables set the maximum time a protective device may take to operate under fault conditions - typically 0.4 s for final circuits up to 63 A on a TN system, with the loop impedance limits tabulated in Tables 41.2 to 41.4.
Section 543 / Table 54.7 - Protective conductors
Section 543 sizes the circuit protective conductor (CPC). Table 54.7 lets you size the CPC by relation to the line conductor, while the adiabatic equation S = √(I²t) ÷ k provides the calculated alternative for verifying that the conductor can withstand the fault energy.
Voltage drop limits
Unlike the NEC, BS 7671 sets recommended voltage-drop limits in its guidance: 3% for lighting circuits and 5% for other uses, measured from the origin of the installation to the load.
Related calculators
Apply BS 7671 in the field with these Voltix calculators.
Voltage Drop Calculator
Check conductor voltage drop for any circuit. NEC, BS 7671 & AS/NZS.
Cable Sizing Calculator
Size cables to carry your load safely under BS 7671 & AS/NZS.
Cable Derating Calculator
Apply temperature and grouping factors to find derated ampacity.
Earthing & Grounding Conductor Calculator
Size protective earthing (BS 7671) and grounding (NEC) conductors.
Take Voltix to the field.
Download the Android app and get 12 professional calculators, offline, always available, across NEC, BS 7671 and AS/NZS.